ROOFTOP Air Conditioners
D4IC-360, 480 (Cool only)
B4IH-360, 480 (Heat pump)
D4IG-360, 480 (Cool only + gas heating)
Technical Information
Vista de página 0
1 2 3 4 5 6 ... 63 64

Resumo do Conteúdo

Página 1 - Technical Information

Ref.: N-27376 1208ROOFTOP Air ConditionersD4IC-360, 480 (Cool only)B4IH-360, 480 (Heat pump)D4IG-360, 480 (Cool only + gas heating)Technical Informati

Página 2

104.3.- Weights of accessoriesModels kg360 480Economiser kg 93 93Fixed manual outdoor air damper kg 75 75Barometric extraction damper kg 64 64Extracti

Página 3

115 - Dimensions, clearances and accesses- Fig. 4 -Models D4IC, D4IG and B4IH(Models only D4IG, see fig. 4B)A1132A5A6 A6YXX17903235003205001815A6A61200

Página 4

12Model D4IG(For further dimensions and details, as per Fig. 4A)- Fig. 4 B -A1A6 A6A22301095G3G3G2G11" BSPFEMALEG1 GAS SUPPLY LINE CONNECTIONG2 A

Página 5 - 3 - Characteristics

135.1.- Applications of upward ducts (bottom) (Fig. 5)1. Return duct: - Access the return section through the access door (A1). - Loosen t

Página 6

145.2.- Application of side ducts (Fig.6)1. Return duct: - Remove and discard the cover (C3). - Connect the duct to the flange provided alo

Página 7 - 3.21.- Sound level

15- Fig. 7 -5.3.- Indoor coil condensed water drain- The condensed water drain line must have a siphon for correct discharge (see Fig. 7).- The diam

Página 8

16- Fig. 8 -CAUTIONWhen connecting the power supply and control wiring to the unit, waterproof type wires must be used to avoid water or humidity ge

Página 9 - 4.2.- B4IH (Heat pump)

178 - Performances D4IC/D4IG8.1.- Cooling capacities D4IC/D4IG-3608.2.- Cooling capacities D4IC/D4IG-480Return airAir temperature in outdoor coil (DB)

Página 10 - 4.4 - Centre of gravity

189 - Performances B4IH9.1.- Cooling capacities B4IH - 3609.2.- Cooling capacities B4IH - 480Data in compliance with EUROVENT conditions.Return airAir

Página 11 - Models D4IC, D4IG and B4IH

199.3.- Heating capacities B4IH - 3609.4.- Heating capacities B4IH - 480Data in compliance with EUROVENT conditions.Conditions out of compressor range

Página 13 - - Fig. 5

2010 - Characteristics of indoor fanDual turbine fan, driven by one single belt drive motor. Motor pulley is of adjustable diameter at ½ turn interval

Página 14 - - Fig. 6

2111.3.- Models 480, applications with vertical ducts (bottom)11.4.- Models 480, applications with horizontal ducts (bottom)12 - Pressure drop of acce

Página 15

2213 - AccessoriesDefinition: "OPTION" are factory fitted items supplied installed on the unit itself and ready for use; "ACCESSORY"

Página 16 - Typical job site wiring

23Dimensions of the economiser/fixed outdoor air intake rain hoodLocation of economiser return air damper- Fig. 9 -- Fig. 10 -2040910OUTDOORAIRRETURNAI

Página 17 - 8 - Performances D4IC/D4IG

2413.2.- Enthalpy sensors for economiserApplicable when requiring an economiser control system that adapts best to the areas in which the humidi

Página 18 - 9 - Performances B4IH

2513.4.- Extraction fan (axial)This is the adequate extraction system when using an econo-miser or motor-driven damper and an extraction of over 25% o

Página 19

2613.5.- Fixed outdoor air intake damperComprises a damper located at the outdoor air intake, and includes the same rain hood and aluminium mes

Página 20 - 11 - Indoor fan performances

2713.14.- FirestatThe unit includes, as standard equipment, an impulse air probe that locks out at 80° C and must be reset manually to resume

Página 21 - 12.2.- Models 480

28- Fig. 15a -Fixed Roof CurbUnit locationDetail of typical Roof Curb application(fixed or adjustable)UNITBASEGASKETROOF INSULATION ANDSEALING MATERIAL

Página 22 - 13 - Accessories

29- Fig. 15b -Adjustable Roof CurbUnit locationType of installation (indicate upon ordering)50 502002960COMPRESSORSIDERETURN SIDERETURNDUCTIMPULSEDUCT

Página 23 - - Fig. 10

37 - Operating limits 168 - Performances D4IC/D4IG 178.1.- Cooling capacities D4IC/D4IG-360 178.2.- Cooling capacities D4IC/D4IG-480 179 - Perfo

Página 24 - - Fig. 11

3014 - Pulley adjustment and belt tensing1.- Adjusting pulley- Loosen the belts. Loosen tensing screw "A".- Loosen studs "B" to

Página 25 - 13.4.- Extraction fan (axial)

3115 - DPC-1 programmable digital ther-mostat with communicationInternal view of the thermostatWith the front cover up, showing the front panel.

Página 26 - - Fig. 13

32Air Conditioning mode key Pressing this key in Normal Mode changes the current air conditioning mode (OFF, COOL, HEAT, AUTO, AUTO PROG, EMERG HE

Página 27

3316.5.- Heating operation sequence with gas (models D4IG)REQUEST FOR HEAT, 1: If the thermostat generates a de-mand for heat, the YKlon board ac

Página 28 - (fixed or adjustable)

34controlled by microswitches (30, 60, 90 minutes). Factory-set to 30 minutes.Defrost can be carried out only when the unit is in heat pump operation.

Página 29 - Adjustable Roof Curb

3517.3.- Low gas pressure (models D4IG)If gas supply pressure falls below the gas pressure switch (GS) set point, power supply to the ignition control

Página 30 - 12 - 14 mm

36- Fig. 18 -- Fig. 19 -ADJUSTMENT OF MAINREGULATORCONNECTINGFLANGE+++PBrADJUSTING FLYWHEEL2ND STAGEV2LOCKSCREWTADJUSTING FLYWHEEL 1STSTAGEV1PIN FOR R

Página 31 - 1 2 3 4 5 6 7

3718.6.- Adjustment gas valve/thermal switchesD4IGmodelBurner modelHeating capacity (kW)Gas typeGas valve adjustments (mbar)Heat switch limits (°C)Tot

Página 32 - 16 - Operation

3819 - Maintenance19.1.- GeneralTo ensure proper operation of the units with minimum energy consumption and a long service life, a maintenance

Página 33 - - Fig. 16

39- Indoor fan belts: Check correct condition and tension. If these are to be replaced, the replacements must be of the same type and size as the ori

Página 34 - 17.1.- Cooling lock-out

413.15.- Copper fin coils 2713.16.- “Blue Fin” coils 2713.17.- Mounting base (Roof Curb), fixed 2713.18.- Mounting base (Roof Curb), adjustable 27 -

Página 35

40siphon are not obstructed. Make sure the water evacuates correctly. Prime the siphon (fill with water) if necessary.- Outdoor coils: Eliminate any d

Página 36 - - Fig. 19

4119.2.- Gas heating units, D4IGMaintenance operations to be carried out by qualified per-sonal at the beginning of the heating season:Gas valve filterC

Página 37 - 18.8- Gas consumption

4219.4.- Cleaning heat exchangerWith adequate combustion regulation, the heat exchanger pipes rarely require cleaning. If there is an accumulation of

Página 38 - 19 - Maintenance

4320- Wiring diagrams20.1.- Cool only models D4IC-360, D4IC-360G50 400.3.50 (1 of 3)         

Página 39 - - Fig. 21

44D4IC-360G50 400.3.50 (2 of 3)  

Página 40 - - Fig. 22

45D4IC-360G50 400.3.50 (3 of 3)      

Página 41 - - Fig. 23

4620.2.- Cool only models D4IC-480, D4IC-480G50 400.3.50 (1 of 3)           

Página 42 - - Fig. 26

47D4IC-480G50 400.3.50 (2 of 3)  

Página 43 - 20- Wiring diagrams

48D4IC-480G50 400.3.50 (3 of 3)      

Página 44 - D4IC-360G50 400.3.50 (2 of 3)

4920.3.- Heat pump models B4IH-360, 400.3.50 (1 of 3)            

Página 45 - D4IC-360G50 400.3.50 (3 of 3)

51 - DescriptionAdequate for installing outdoors, either on the roof or on ground level.The D4IC series are cool only versions, but accept el

Página 46

50B4IH-360, 400.3.50 (2 of 3)  

Página 47 - D4IC-480G50 400.3.50 (2 of 3)

51B4IH-360, 400.3.50 (3 of 3)      

Página 48 - D4IC-480G50 400.3.50 (3 of 3)

5220.4.- Heat pump models B4IH-480, 400.3.50 (1 of 3)          

Página 49

53B4IH-480, 400.3.50 (2 of 3)  

Página 50 - B4IH-360, 400.3.50 (2 of 3)

54B4IH-480, 400.3.50 (3 of 3)      

Página 51 - B4IH-360, 400.3.50 (3 of 3)

55              

Página 52

56  

Página 53 - B4IH-480, 400.3.50 (2 of 3)

57         

Página 54 - B4IH-480, 400.3.50 (3 of 3)

58       

Página 55

59

Página 56 - D4IG-360, 400.3.50 (2 of 4)

6This aluminium surface causes minimum friction with the air, and is easy to clean.3.4.- Base beams The base beams are fixed and provide a foundation f

Página 57 - D4IG-360, 400.3.50 (3 of 4)

60  

Página 58 - D4IG-360, 400.3.50 (4 of 4)

61         

Página 59

62      

Página 60 - D4IG-480, 400.3.50 (2 of 4)

63Configuration of switchesData and dimensions are subject to change without prior notice.

Página 62 - D4IG-480, 400.3.50 (4 of 4)

7the outdoor coil.On units with several compressors, it cannot defrost two circuits at the same time.3.19.- Transportation and handlingSuspend

Página 63 - Configuration of switches

84 - Technical specifications and physical data4.1.- D4IC (Cool only) and D4IG (Cool only + gas heating)(1) Data in compliance with Eurovent. Summer:

Página 64

94.2.- B4IH (Heat pump)(1) Data in compliance with Eurovent. Summer: Indoor DB 27° C / WB 19° C, outdoor DB 35° C. Winter: Indoor DB 20° C, outdoor